Dynamical Analysis of Power System Cascading Failures Caused by Cyber Attacks

More Info
expand_more

Abstract

Cascading failures in power systems are extremely rare occurrences caused by a combination of multiple, low probability events. The looming threat of cyberattacks on power grids, however, may result in unprecedented large-scale cascading failures, leading to a blackout. Therefore, new analysis methods are needed to study such cyber induced phenomena. In this article, we propose a data-driven method for dynamical analysis of power system cascading failures caused by cyberattacks. We provide experimental proof on how attacks may accelerate the cascading failure mechanism, in comparison to historically observed blackouts. Using a dynamic power grid model, consisting of multiple, coordinated protection schemes, we define and analyze the point of no return in a cascading failure sequence by applying the Hilbert-Huang transform for time-frequency analysis. Numerical results indicate, cyberattacks may accelerate cascading failures at least by a factor of 3x. This is due to the excitation and non-damping of multiple frequency modes greater than 1 Hz in a short time span. The proposed method is tested using time domain simulations conducted through a modified IEEE 39-bus test system, which can simulate cascading outages using coordinated protection schemes.