Active filter parameter tuning method for harmonic voltage mitigation in wind power plants

More Info
expand_more

Abstract

It is challenging to determine the active filter control factors in wind power plants (WPP) to obtain effective harmonic voltage mitigation and avoid over-modulation or system instability problems caused by overlarge feedforward or feedback gains. To address this issue, an active filter tuning (AFT) method is proposed in this paper to offer a common parameter tuning and stability assessment strategy for both current-controlled and voltage-controlled harmonic impedance reshaping (HIR) methods by introducing a coordination factor including different weight coefficients for system stability margin, wind turbine (WT) harmonic suppression, and grid harmonic mitigation. The superiority of the proposed method is verified in a 20 MW WPP with four cases considering both WT harmonic voltage amplification and grid voltage amplification. Compared to previous methods, the AFT-based HIR method achieves a more flexible balance between system stability and harmonic voltage mitigation, obtaining better performance in WT harmonic suppression, grid harmonic suppression, system robustness, and transient response.