High penetration of distributed generation (DG) has led to frequent voltage fluctuations in the distribution network. This paper describes the design of a partially rated, power-electronic-assisted onload tap-changing (OLTC) autotransformer. Positive and negative compensation of
...
High penetration of distributed generation (DG) has led to frequent voltage fluctuations in the distribution network. This paper describes the design of a partially rated, power-electronic-assisted onload tap-changing (OLTC) autotransformer. Positive and negative compensation of the grid voltage can be achieved on feeders that have high distributed generation and/or loading. A novel design of taps comprised of several no-load switches and a single semiconductor-mechanical hybrid switch have been proposed, that requires reduced voltage rating and a number of switches. In steady state, the mechanical switch in the hybrid switch conducts the load current resulting in low steady-state losses. During the tap change process, the OLTC uses semiconductor switches, namely insulated-gate bipolar transistor /metal-oxide semiconductor field-effect transistor, thus achieving arc-free tap change and long lifetime of switches. The OLTC system has been customized for both low-voltage and medium-voltage three-phase distribution networks. An open-delta configuration for the medium-voltage application has been proposed that requires only two OLTC units to control all three line voltages. Simulations are carried out to verify the steady-state and transient operation of the proposed OLTC.@en